The "Relay/Controls" menu
126
Selection:
actual value (default)
The relay switches according to the current measuring value (although its reliability is not
ensured).
hold
The current switching state of the relay is held.
switch on
The relay is energized.
switch off
The relay is de-energized.
8.5.6 "relay allocation"
Allocates a relay to the rake control function.
Selection:
All relays of the instrument version at hand.
8.5.7 "relay N" (N = 1 - 6)
"function"
Allocates the desired function to the relay.
Selection:
none (default)
rake control
"invert"
Determines if the switching behavior of the relay is to be inverted.
Selection:
no (default)
The switching behavior of the relay is not inverted. The relay is energized if the rake cleaner
should be switched on.
yes
The switching behavior of the relay is inverted. The relay is energized if the rake cleaner should
be switched off.
relay allocation RX203
relay 1
relay 2
relay 3
relay 4
RelaisN RN306
function:
invert: