The "Relay/Controls" menu
81
8.2 Configuration of an alarm or diagnostic relay
8.2.1 Overview
8.2.2 "relay allocation"
Use this parameter to select the relay you are going to configure.
Selection:
• All relays of the instrument version at hand
!
Note!
If a function has already been allocated to one of the relays, the name of this function is displayed
next to the relay number.
8.2.3 "relay N" (N = 1 - 6)
(Part 1: relay function)
After selecting a relay, the parameter set "relay N" (N =1 - 6) appears, which is used to configure
the relay. Initially, it contains only the "function" parameter. To configure an alarm relay or
diagnostic relay, proceed according to the following steps:
1. Select the "function" parameter. The "select function" screen appears.
2. Select "alarm/diagnostics". The "function" selection list appears.
Step Parameter set or submenu Parameter Remark see section
1 "relay controls" menu Select "relay configuration"
2 relay allocation Select a relay 8.2.2
3 relay N (N= 1 -6) function 1. Select "alarm/diagnostics"
2. Select
– "alarm relay", if the relay is to indicate an alarm state of the
Prosonic S.
1)
– "diagnostics", if the relay is to indicate one or two user selectable
states of the instrument.
8.2.3
4 relay N (N = 1 - 6) allocation 1 Select the first instrument state which is to be indicated by the relay.
(only available if "diagnostics" has been selected in the previous function)
8.2.4
allocation 2 Select the second instrument state which is to be indicated by the relay.
(only available if "diagnostics" has been selected in the previous function)
5 relay N (N = 1 - 6) invert Select if the relay signal is to be inverted (default: no) 8.2.5
1) This is the default setting for relay 1.
⇒
relay allocation RX101
relay 1
relay 2
relay 3
relay 4
⇒
relay 1 R1103
function: