The "Relay/Controls" menu
81
8.2 Configuration of an alarm or diagnostic relay
8.2.1 Overview
8.2.2 "relay allocation"
Use this parameter to select the relay you are going to configure.
Selection:
All relays of the instrument version at hand
!
Note!
If a function has already been allocated to one of the relays, the name of this function is displayed
next to the relay number.
8.2.3 "relay N" (N = 1 - 6)
(Part 1: relay function)
After selecting a relay, the parameter set "relay N" (N =1 - 6) appears, which is used to configure
the relay. Initially, it contains only the "function" parameter. To configure an alarm relay or
diagnostic relay, proceed according to the following steps:
1. Select the "function" parameter. The "select function" screen appears.
2. Select "alarm/diagnostics". The "function" selection list appears.
Step Parameter set or submenu Parameter Remark see section
1 "relay controls" menu Select "relay configuration"
2 relay allocation Select a relay 8.2.2
3 relay N (N= 1 -6) function 1. Select "alarm/diagnostics"
2. Select
"alarm relay", if the relay is to indicate an alarm state of the
Prosonic S.
1)
"diagnostics", if the relay is to indicate one or two user selectable
states of the instrument.
8.2.3
4 relay N (N = 1 - 6) allocation 1 Select the first instrument state which is to be indicated by the relay.
(only available if "diagnostics" has been selected in the previous function)
8.2.4
allocation 2 Select the second instrument state which is to be indicated by the relay.
(only available if "diagnostics" has been selected in the previous function)
5 relay N (N = 1 - 6) invert Select if the relay signal is to be inverted (default: no) 8.2.5
1) This is the default setting for relay 1.
relay allocation RX101
relay 1
relay 2
relay 3
relay 4
relay 1 R1103
function: