The "output/calculations" menu
132
9.3 "HART settings" submenu
(only for current output 1)
9.3.1 "HART settings"
"HART address"
Defines the communication address for the instrument.
Range of values:
for standard operation: 0 (default)
for multidrop operation: 1 - 15
!
Note!
In multidrop operation, the ouptput current is 4 mA by default. However, it can be adjusted in the
"mA value" parameter of the "mode current" parameter set (see above).
"no. of preambles"
Specifies the number of preambles for the HART protocol. For lines with communication problems
a slight increase of this value is recommended.
"short TAG HART"
in preparation
HART settings O1203
HART address:
no. of preambles:
short TAG HART: