The "Relay/Controls" menu
82
3. Select
"alarm relay", if the relay is to indicate an alarm state of the Prosonic S
5)
.
"diagnostics" if the relay is to indicate one or two user selectable states of the instrument.
8.2.4 "relay N" (N = 1 - 6)
(Part 2: Allocation of the switching condition)
"allocation 1/2"
A specific instrument state or event can be allocated to each of these parameters. The relay is de-
energized as soon as one of these states or events occurs.
Selection:
echoloss sensor 1/2/1+2
defective temperature sensor1/2
defective external temperature sensor
Accumulated alarm: defective temperature sensor
•overtemp. sensor 1/2
Accumulated Alarm: overtemp.
safety distance channel 1/2
Accumulated Alarm: safety distance
•pump alarm
pump operation
8.2.5 "relay N" (N = 1 - 6)
(Part 3: Relay behavior)
"invert" subfunction
Use this parameter to specify if the switching direction of the relay is to be inverted.
Selection:
no (default)
The switching direction of the relay is not inverted. The relay switches as described in the above
sections.
yes
The switching direction of the relay is inverted. The states "energized" and "de-energized" are
interchanged as compared to the above description.
5) This is the default setting for relay 1.
relay N RN103
function: diagnostics
allocation 1:
allocation 2:
relay N RN104
invert: