Installation
16
3.3.2 Installation conditions
• The DIN-rail housing must be mounted outside hazardous areas in a cabinet.
• The housing is mounted on a DIN rail EN 60715 TH 35x7,5 or TH 37x15.
• Do not install the instrument in the vicinity of high-voltage lines, motor lines, contactors or
frequency converters. The installation regulations for high-voltage lines, motor lines, contactors
or frequency converters must be observed.
• To ensure easy mounting and opening of the housing, a distance of approx. 1 cm should be kept
between the instruments.
• In order to avoid interference signals, the sensor cables must not be laid parallel to high voltage
or electric power lines.
• The cables may not be laid in the proximity to frequnecy converters.
3.3.3 Mounting
L00-FMU90xxx-17-00-00-xx-001
A: Attaching the instrument to the rail; B: Detaching the instrument from the rail
a
b
EN 60715 TH 35x7,5
EN 60715 TH 35x15
A
B
b
a