Commissioning
56
Step Parameter Set Parameter Remarks s. section
Interference echo suppression
7 distance correction act. distance 1
act. distance 2
Indicates the currently measured distance between the sensor membrane
and the product surface.
6.4.8
6.4.9
Check distance Compare the indicated distance with the real value:
"distance = ok" "distance mapping" (see below)
"distance too small" "distance mapping" (see below)
"distance too big" Basic setup completed
"distance unknown" Basic setup completed
"manual" "distance mapping" (see below)
8 distance mapping act. distance 1
act. distance 2
Indicates the currently measured distance between the sensor membrane
and the product surface.
6.4.10
range of mapping Determines the range over which the mapping is recorded;
confirm the predefined value or enter your own value.
start mapping Select:
no: the mapping is not recorded
yes: the mapping is recorded; after completion the "LVL 1(2) state" func-
tion appears (see below)
9 LVL 1(2) state level 1(2) Indicates the currently measured level. 6.4.11
act. distance Indicates the currently measured distance between the sensor membrane
and the product surface. Check the value:
Value correct: Basic setup completed.
Return to the measured value display by pressing several times
Value not incorrect: go back to step 7 ("distance correction")
status Used to enable, disable or delete a mapping