RMS 621 10 Technical data
Endress+Hauser 63
Fig. 26: External display and operating unit for panel mounting (optional or available as accessory); dimensions in mm
(inches)
Operating elements Eight front-panel soft keys interact with the display (function of the keys is shown in the display).
Remote operation RS232 interface (3.5 mm (0.138 in) jack plug on front panel): configuration via PC with PC
operating software ReadWin
®
2000.
Real time clock Deviation: 2.6 min per year
Power reserve: 14 days
Mathematical functions Continuous calculation of dimensions, standard volumes, density, enthalpy, quantity of heat via
IAWPS-IF97
10.0.9 Certificates and approvals
CE approval The measurement system fulfils the requirements demanded by the EU regulations.
Endress+Hauser acknowledges successful unit testing by adding the CE mark.
Other standards and
guidelines
EN 60529:
Degrees of protection by housing (IP Code)
EN 61010:
Safety requirements for electrical measurement, control and laboratory instrumentation.
EN 61326 (IEC 1326):
Electromagnetic compatibility (EMC requirements)
NAMUR NE21, NE43
Standardization association for measurement and control in chemical and pharmaceutical
industries.
IAWPS-IF 97
International applicable and recognised calculation standard (since 1997) for steam and water.
Issued by the International Association for the Properties of Water and Steam (IAPWS).
OIML R75
International construction regulation and test specification for water energy managers from the
Organisation Internationale de Métrologie Légale.
EN 1434 1, 2, 5 and 6
EN ISO 5167
Flow measurement of fluids with throttle devices