6 Electrical connection
6�1 Connection requirements
Please note the following points before connecting up the device:
•Thevoltagesupplymustmatchthevoltagespeciedonthenameplate.
•Switchothesupplyvoltagebeforeconnectingthedevice.
Connect a potential matching line to the terminal to be used on the device before connecting
to the power supply.
•Whenconnectingtothepublicpowersupply,apowerswitchforthedevicemustbeinstalled
withineasyreachofthedevice.Theswitchistobeidentiedasadisconnectingdevicefor
the device (EN/IEC 61010).
•Thecableglandsandconnectorsarepermittedforconnectingxedcablesandlinesonly.
The operator must ensure adequate strain relief.
The device is to be attached so that the cable gland is protected from mechanical damage
(degree of mechanical hazard "low" – impact energy: 4 joules).
•Unusedguideopeningsmustbesealedousingsealingplugs,theplastictransportsealing
plug does not meet this requirement and must therefore be replaced during installation.
Fordevicesintendedforuseinhazardousareas,pleasereadtheinformationandcomply
withtheinstructionsintheExdocumentation(XA).
6�1�1 Required tools
For the terminals:
0.6 x 3.5 mm
For the cable gland:
25 mm (AF) (plastic) or 22 mm (AF) (metal)
6�1�2 Connecting cable requirements
Theconnectingcablesprovidedbythecustomermustfullthefollowingrequirements:
• Electrical safety in accordance with applicable national regulations.
• Permitted temperature range→52
• Normal installation cable with at least three wires
• Cable cross-sections: 0.2 to 2.5 mm
2
(24 to 12 AWG)
For the optionally supplied mating connectors,thefollowingrequirementsapply:
Clamping range of the cable:
-6...8mm(M12matingconnector,Binderseries713/763)
- 7 ... 10.5 mm (Harting HAN8D mating connector)
Cable cross-section: max. 0.75 mm
2
(18 AWG)
For the electrical connection with connectors there are prefabricated connecting cables
availableasaccessories.→51