Soliwave FQR56/FDR56
Commissioning
Endress+Hauser 43
8�6 Simulation
TheFDR56givesyoutheabilitytosimulateasignalandtherebyanoutputvariable,
independentoftheprocess,forexample,inordertocongureadownstreamPLCoradata
logger.
The simulation is carried out as follows:
Move the encoding switch to position 9
→Displayofthefunctionnumber
→Aer2seconds:Displayofthesimulatedsignalstrength
(signalstrength=0LEDs,switchoutput:notswitched,
current output: 4 mA)
Press the or keyonthedevicetocongurethedesiredsignalstrength
→Displayofthechangedsimulatedsignalstrength,example:
(signalstrength=8LEDs,switchoutput:switched,
current output: 16.8 mA)
Move the encoding switch to the initial position 0
→Displayofthecurrentsignalstrength
The simulation ends as soon as the encoding switch is no longer at position 9.