Soliwave FQR56/FDR56
Electrical connection
28
Endress+Hauser
6�3�4�2 Solid-state relay
3
4
The following characteristic data apply for the solid-
state relay signal output (switching contact of a
semiconductor relay):
Switching capacity: 30 V / 0.4 A or 40 V / 0.4 A
• Switching frequency: max. 4 Hz
Electrical connection Solid-state relay
Connection terminals Terminal3−4
M12 connector (Binder series 713/763) Connector2,contact3−4
Harting connector type HAN8D Connector2,contact3−4
The polarity of the solid-state relay can be set as required.
6�3�4�3 Current output
A
+
-
3
4
The following characteristic data apply for the current
output:
•4-20mA,active
•Max.load:600Ω
Electrical connection Current output
Connection terminals Terminal3(+)−4(−)
M12 connector (Binder series 713/763) Connector2,contact3(+)−4(−)
Harting connector type HAN8D Connector2,contact3(+)−4(−)