Soliwave FQR56/FDR56
Commissioning
Endress+Hauser 39
Thelimitsignalfunctionisconguredasfollows:
Move the encoding switch to position 6
→Displayofthefunctionnumber
→Aer2seconds:Displayoftheconguredlimitsignalfunction,example:
Press the or key on the device in order to change between the two possible limit
signal functions
→Displayofthechangedlimitsignalfunction,example:
Move the encoding switch to the initial position 0
→Displayofthecurrentsignalstrength
Output Rest
position
Setting Exceeding of
switch point
(LED 5)
Undershooting
hysteresis
(function 5)
Relay
(Contact 3-4-5)
or
Solid-state
relay
(Contact 3-4)
3 4 5
3 4 5 3 4 5
3 4 5 3 4 5
These settings are for adapting the switching function to the downstream analysis (process
control system).
•Thissettinghasnosignicanceforthecurrentoutput.
8�4�3 Switching delay (function 7 and 8)
Anadditionalswitch-onand/orswitch-odelaycanbeconguredfortheswitchoutput.
Thiscanbeused,forexample,tostabilizetheswitchoutputwhenthesignalstrength
uctuatesgreatly,sothattherelaydoesnotswitchuntiltheswitchpointhasbeenexceeded
orundershotforacorrespondingtime.
Aslongasthetimes,inwhichamaximumlimitisundercut,aresmallerthantheswitch-o
delays,theswitchoutputremainsinthe"uncoveredstate".
Thefollowingguredependsonthesettingofthelimitsignalfunction(function6)