Soliwave FQR56/FDR56
Commissioning
Endress+Hauser 41
•Thedelaysimpactonlytheswitchoutputs(relayandsolid-staterelay);theyhaveno
signicanceforthecurrentoutput.
•Iftheentirebulksolidsdetection(includingthesignalstrengthdisplay)istobestabilized,
itisadvisabletoenteran(additional)damping(averagingoverasettime,seefollowing
section).
8�4�4 Damping (function A)
Forunstableprocessconditions,thedisplayofthesignalstrengthcanbestabilizedbya
congurabledamping;averagingoftheoutputsignaltakesplacehereoverthesettime.
Setting Damping Setting Damping
off 2 s
100 ms 3 s
200 ms 5 s
300 ms 10 s
500 ms 20 s
1 s
Thedampingisconguredasfollows:
Move the encoding switch to position A
→Displayofthefunctionnumber
→Aer2seconds:Displayofthecongureddamping,example:
(damping=200ms)
Press the or keyonthedevicetocongurethedamping
→Displayofthechangeddamping,example:
(damping increased to 500 ms)
Move the encoding switch to the initial position 0
→Displayofthecurrentsignalstrength
•Thesettimenotonlydampsthesignalstrengthdisplay,butalsoimpactstheswitchoutput
(forexample,adelayedswitching)andthecurrentoutput(rises/fallswithadelay).
•Ifonlytheswitchoutputistobestabilized,itisadvisabletocongureaswitch-onand/oro
delay(→39).
•Theswitch-onand/orodelayanddampingcanbecombined,whichcausesthedetection
tobesignicantlyslower.