User GuideCordex® CXPS-E105 Edge Power Systems
4.3 Cordex® HP rectifiers
4.3.1 Cordex® HP 2.4 kW rectifier (option)
Rectifier features
• High performance compact 50 A rectifier for 48 Vdc Telecom applications
• High eciency (96.2 percent) for reduced OPEX and carbon footprint
• High temperature operating range for installation in non-controlled environments
• Multiple configurations providing up to 250 A or 12 kW in a compact 1RU form factor
• High power density (28 W/in
3
) yields more space for revenue generating equipment
• Wide AC input operating range for global installation requirements
• Extended operating temperature range up to 75°C (167°F) for deployment in the harshest outdoor
environments
4.3.2 Cordex® HP 3.0 kW rectifier (option)
Rectifier features
• High performance compact 62.5 A rectifier for 48 Vdc Telecom applications
• High eciency (96.5 percent) for reduced OPEX and carbon footprint
• High temperature operating range for installation in non-controlled environments
• Multiple configurations providing up to 312 A or 15 kW in a compact 1RU form factor
• High power density (35 W/in³) yields more space for revenue generating equipment
• Wide AC input operating range for global installation requirements
• Extended operating temperature range up to 75°C (167°F) for deployment in the harshest outdoor
environments
4.3.3 Front panel LEDs
The front panel LEDs indicate the rectifier status summary and patterned response to Locate Module command.
Alarm/Fault
The red LED is on during an active Module Fail alarm if the module is unable
to source power due to a fault condition. Refer to the relevant controller
manual for fault details.
The LED flashes (~2 Hz) when a minor alarm is detected if the module's
output capability has been reduced or a minor failure is detected.
The red LED will remain active if the module is receiving power from the DC
bus.
DC ON
The green LED is on when the rectifier is delivering power to the load. The
LED goes out when the rectifier is o. For example, when commanded by the
controller.
AC ON
The green LED is on when the AC input voltage is qualified and within the
operational AC input range and input frequency.
LED activity during the Locate Module command from controller
The Locate Module command from the controller, causes the LEDs of the target rectifier to flash in a cyclical
pattern. This flashing normally lasts 60 seconds.