www.enersys.com
TABLE 2
Base Beam Anchor Spacing
Cell
Model
2 Cells
Wide
3 Cells
Wide
4 Cells
Wide
6 Cells
Wide
Multi-Stack
w/zero
separation
L (in) L (in) L (in) L (in) M (in)
35-07 6.04 N/A 10.52 15.01 L+0.89
50-09 9.04 N/A 16.52 24.01 L+0.89
50-13 12.04 N/A 22.52 33.01 L+0.89
50-17 15.49 22.48 29.26 43.17 L+0.89
85-13 12.04 N/A 22.52 33.01 L-2.95
85-15 13.54 N/A 25.52 37.51 L-2.95
85-21 18.48 26.93 35.26 53.71 L-2.95
85-25 21.48 31.43 41.26 42.68 L-2.95
85-27 22.98 33.69 44.27 67.22 L-2.95
85-33 27.48 40.43 53.26 80.71 L-2.95
100-21 18.48 26.93 35.26 53.71 L-2.95
100-25 21.48 31.43 41.26 62.68 L-2.95
100-27 22.98 33.69 44.27 67.22 L-2.95
100-33 27.48 40.43 53.26 80.71 L-2.95
125-25 22.09 31.88 41.98 63.29 L-4.24
125-27 23.59 34.14 44.98 67.83 L-4.24
125-33 28.09 40.88 53.98 81.32 L-4.24
Anchor Spacing
EXAMPLE:
If you are installing a DDm85 MULTI-STACK WITH ZERO SEPARATION and you have 21 plates/cell, 4 cells wide.
10
M (inches) = L (in) - 2.95”
35.26” - 2.95” = 32.31”