4 Controller
EMW90HDNC1A Air-cooled Chiller
21
Parameter
Default Value
Setting Range
Unit
Description
and off conditions of heating.
Heat Sens
3
[1~10]
°C
Outlet High
Temp Sp
30
[0~55]
°C
When the system detects that
the current outlet coolant
temperature is higher than the
value of this parameter, it
judges that the outlet coolant
temperature is too high.
Outlet Low
Temp Sp
-5
[-30~55]
°C
When the system detects that
the current outlet coolant
temperature is lower than the
value of this parameter, it will
judge that the outlet coolant
temperature is too low.
Control Temp
Monitor Temp
Monitor Temp
Sup Water
-
Identifies the type of
temperature controlled by the
system.
Monitor Temp: The system
controls according to the
outlet coolant temperature.
Sup Water: The system
controls according to the cell
temperature sent by the host
computer during
communication.
The default values and value ranges of the above parameters are for reference only, and the factory settings shall prevail.
(Optional) Team Setting
When supporting the group control function, the operator
must make the relevant group control setting after the
chiller is powered on for the first time and runs normally,
otherwise the group control function will not be realized,
and the chiller will return to the independent operation
control mode.
Group control can improve the efficiency of
chillers and avoid the competition between
chillers by cascading multiple chillers.
Group control function is an optional function.
When the group control function is not provided,
the values of the parameters in the Team Setting
interface are displayed as "****", as shown in
Figure 4-15.
Parameter
Description
Team
Set to Team when supporting
group control function.