EMW90HDNC1A Air-cooled Chiller
Inspection and Maintenance
Replace the pump.
Please refer to 7.4.3 Replacing the
Electrical Heater and Circulation Pump for
specific operation.
Electrical heater
does not work
Check the outlet coolant temperature, and
whether the heating set point is set
reasonably.
Fasten the circuit connector.
Electrical heater overheat
protection
After waiting for a period of time, restart the
electrical heater and observe whether the
electrical heater works normally.
Replace the electrical heater.
Please refer to 7.4.4 Replacing the
Electrical Heater and Circulation Pump for
specific operation.
The main parts and their locations in the EMW90HDNC1A chiller are shown in Figure 7-1.
Figure 7-1 Parts description