5 Coolant Filling and Replenishment
EMW90HDNC1A Air-cooled Chiller
25
5 Coolant Filling and Replenishment
Prerequisites
The pipe connection of the coolant circulation
system has been completed.
The vacuum pump and the coolant filling pump
are ready.
Precautions
It is forbidden to run the chiller in a scenario
where no coolant is added.
The maximum pressure-bearing design of the
pipeline of the coolant circulation system of the
chiller is 10 bar. It is recommended that the
static pressure of the circulation system be
controlled between 0.8 bar and 1 bar after
coolant filling. Please pay attention to the
pressure control when using an external
coolant filling kit for coolant filling.
When adding coolant to the chiller, it is
recommended to equip a filter screen with a
size of 30 mesh or above to prevent dust and
other impurities from entering the coolant
circulation system.
When using water-glycol mixed coolant,
please refer to Table 8-1 to check whether the
coolant specifications meet the requirements.
During use, it is necessary to regularly check
the quality of the coolant and deal with it to
avoid abnormalities such as precipitation,
which will affect the performance of the chiller.
The coolant must have low hardness (calcium
hardness), otherwise it will cause scale
precipitation or loose layering, and the coolant
cannot be soft water. Up to 50% of the volume
fraction of ethylene glycol aqueous solution is
allowed.
During the long-term use of the chiller, the
concentration of the coolant becomes higher,
which will reduce the cooling efficiency of the
chiller. It is recommended to check the coolant
concentration in the circulation system of the
chiller every 3 months. If the coolant
concentration is too high, the value can be
restored to the normal range by completely
replacing the coolant.
During the long-term use of the chiller, the
coolant may appear mechanical dirt, high
hardness, high chemical dirt content,
biological dirt, slime bacteria, and algae. It is