User Manual
6 Routine Maintenance
EMW90HDNC1A Air-cooled Chiller
29
6.5 Condenser Maintenance
The edges of the condenser blades are sharp, please wear gloves for operation.
Routine maintenance of condenser is shown in Table 6-4.
Table 6-4 Condenser maintenance
Maintenance
Item
Maintenance
Standard
Maintenance
Cycle
Detection
Mode
Troubleshooting
Condenser
cleaning
Condenser is free
from dust and
foreign matter
blockage
6 months
Visual
inspection
Clean the condenser with
compressed air or a
vacuum with a brush head
after 10 minutes of power
off.
Fins are not
seriously deformed
3 months
Visual
inspection
Use tools such as a fin
comb to correct it after 10
minutes of power off.
The above maintenance intervals are only recommended values, you can adjust them according to actual planning.
6.6 Coolant Maintenance
Routine maintenance of coolant is shown in Table 6-5.
Table 6-5 Coolant maintenance
Maintenance
Item
Maintenance
Standard
Maintenance
Cycle
Detection
Mode
Troubleshooting
Cooling medium
Concentration
meets range
requirements
The PH value and
the concentration
of each electrolyte
meet the
requirements.
No dirt,
precipitation,
algae, etc.
3 months
Coolant
tester
Visual
inspection
Replace the coolant after
power off.
The above maintenance period is only a suggested value, and user can adjust it according to the actual performance of
the coolant. The maintenance cycle of the coolant with better stability can be relatively extended.