8.2 Coolant Specifications
The specifications of the coolant used in the
air-cooled chiller must meet the requirements of
Table 8-1.
Table 8-1 Coolant specifications
Parameter
Value
PH
(7) 7.5-8.5
Conductivity
200-1000 μS/cm
Evaporation
residue
< 500 mg/dm³
Sedimentary
material
< 3 mg/dm³
Hardness
3-8°dH (for
German-speaking regions)
Ca + Mg
0.5-2 mmol/l (for
international regions)
Bicarbonates
1-5 mmol/dm³ (60-300
mg/dm³)
Free carbon
monoxide
< 10 mg/dm³
Sulfide
< 0.01 mg/d
Chloride
< 50 mg/dm³
Parameter
Value
Sulfate
< 250 mg/dm³
Nitrate
< 25 mg/dm³
Nitrite
< 0.1 mg/m³
CSB
< 7 mg/dm³
NH4
< 0.05 mg/d
Fe
< 0.1 mg/dm³
Mn
< 0.1 mg/dm³
Cu
< 0.1 mg/dm