General safety instructions
Receptacles may not be installed inside the sauna cabin.
Each sauna cabin must have air inlets and outlets. The air inlets
and outlets may be installed below or behind the sauna heater,
approx. 5–10 cm/2–4 inches above the floor. The minimum di-
mensions of the air inlets and outlets can be found here:
2.4 Technical data, EN-17, 3.1.3 Air inlets and outlets,
EN-25.
The exhaust openings are always installed in the lower part of
the wall diagonal to the sauna heater. The supply and exhaust
openings must not be closed. Please observe the instructions
provided by your sauna cabin manufacturer.
Use one of the control units listed below to check and control
the sauna heater. This control unit is fixed to a suitable location
on the cabin’s external wall, and the corresponding sensor
housings according to the installation instructions that accom-
pany the control units inside the sauna cabin.
The cabin lighting must be safe for sauna cabin use and in-
stalled in such a way that it can be used safely in a sauna cabin.
Ensure that the heater is installed in compliance with the stan-
dards and legal norms valid in your country.
The cabin door must open outward and must not have a lock
that cannot be opened in the case of failure. We recommend
magnetic or spring locks.