EasyManua.ls Logo

Epever UP2000-HM6021 - Page 16

Epever UP2000-HM6021
64 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
14
2) AC Load
Recommended wire size of the AC load and the circuit breaker is as below.
Model
Load wire size
Circuit breaker
Torque
UP2000-HM6021
6mm
2
/9AWG
2P40A
1.2N.M
UP2000-HM6022
3.4mm
2
/12AWG
2P16A
1.2N.M
UP3000-HM5041
6mm
2
/9AWG
2P40A
1.2N.M
UP3000-HM5042
4mm
2
/11AWG
2P25A
1.2N.M
UP3000-HM8041
6mm
2
/9AWG
2P40A
1.2N.M
UP3000-HM10021
6mm
2
/9AWG
2P40A
1.2N.M
UP3000-HM10022
4mm
2
/11AWG
2P25A
1.2N.M
UP5000-HM8042
6mm
2
/9AWG
2P40A
1.2N.M
Making the connection wire of the AC load:
Strip the AC load connection wires (3 pcs) for about 10 mm.
Symbols
Abbreviation
Name
Color
L
LINE
Live wire
Brown/black
N
Neutral
Neutral line
Blue
Ground line
Yellowish green
3) PV modules
Recommended wire size of the PV module and the circuit breaker is as below.
Since the PV array's output current varies with the type, connection method, or sunlight angle, its minimum
wire size can be calculated by the short circuit current(ISC). Please refer to the ISC value in the PV
module's specifications. When the PV modules are connected in series, the total ISC equals any PV
module's ISC. When the PV modules are connected in parallel, the total ISC equals all PV modules' ISC.
Please refer to the table below:
Model
PV wire size
Circuit breaker
UP2000-HM6021
6mm
2
/9AWG
2P40A
UP2000-HM6022
4mm
2
/11AWG
2P25A
UP3000-HM5041
6mm
2
/9AWG
2P40A
UP3000-HM5042
6mm
2
/9AWG
2P40A
UP3000-HM8041
10mm
2
/7AWG
2P50A
UP3000-HM10021
6mm
2
/9AWG
2P40A
UP3000-HM10022
6mm
2
/9AWG
2P40A
UP5000-HM8042
6mm
2
/9AWG
2P40A

Related product manuals