[BufferFlex] function block - log boiler ETAtouch controller
7.3.3.1 Setting the hot water charging times
Opening charging times and temperature for hot
water with a combination tank
The charging times for the hot water and the set tem-
peratures can be adjusted in the settings ( button).
To adjust, open the settings and then open the
charging times of any given day with the [Hot water
Charging times Daily plan] button. An overview screen
opens.
Fig. 7-51: Overview
1 Set time window (charging times)
2 Select day of the week
3 Add another time window
4 Graphical representation of the time window
setting
5 Overview of all time windows for the entire week
6 Delete time window
7 Adjustable hot water temperature within the time
window
8 Period of the time window
9 Set-back temperature of the hot water outside the
time window
Setting the time window and copying to other
days of the week is described in chapter 7.1.6.6
"Setting a time window".