EasyManua.ls Logo

eta SH20 - Text Menu - Adjustable Parameters

eta SH20
80 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ETAtouch controller [Heating circuit] function block
59
Setting heating limits for the reduced operation
mode
1. Change the selector switch to the reduced
operation mode position ( ).
Use the arrow keys to reduce parameter [Heating
threshold], so that the heating circuit in reduced
operation mode switches off at a lower outside
temperature, or increase the value.
At settings below 0 °C, there is a risk of
freezing.
Fig. 7-67: Heating limit for reduced-temperature mode
7.6.4 Text menu - Adjustable parameters
Adjustable parameters
Detailed descriptions of the parameters are provided
below.
Explanation of [Room effect]
Optional: only for room sensor
The flow temperature is calculated on the basis of the
heating curve and the outside temperature. If the room
temperature falls by 1°C, the target flow temperature is
increased by this set value. If the room temperature
rises by 1°C, the target flow temperature is decreased
by the set value.
For underfloor and wall heating with a design
temperature of 30 °C, set the room influence to 1
°C; with a design temperature of 40 °C, set it to 2 °C.
Explanation of [Switch-on diff. room] and [Switch-
off diff. room]
Optional: only for room sensor
These parameters specify the allowed deviation of the
set room temperature for switching the heating circuit
on and off.
Example:
Room temperature setting = 21 °C
[Switch-on diff. room] = 0.5 °C
[Switch-off diff. room] = 2 °C
=> The heating circuit will be switched off as soon as
the room temperature reaches 23 °C (=21 + 2 °C). If
the room temperature falls to 21.5 °C (=21+0.5 °C),
heat is supplied to the heating circuit again.
Heating circuit
Room
Room effect
Switch-on diff. room
Switch-off diff. room

Table of Contents

Related product manuals