EVCO S.p.A.
c-pro 3 nano CHIL | Application manual ver. 1.0 | Code 144CP3NCHE104
page 23 of 90
1 = workday 1
2 = workday 2
Level
1
USER MENU
ModE
Set the operating mode:
0: Cold, (chiller/summer)
1: Hot (heat pump/winter)
0 0 1 UT
Modifiable only if the unit is a
chiller + heat pump:
(PG00=2,4)
SPC1
Set the value of the summer setpoint
(chiller)
8.5 PC21 PC22 °C UT
SPH1
Set the value of the winter setpoint
(heat pump)
44.0 PC23 PC24 °C UT
PUC1
Offset for the summer setpoint from
digital input
2.0 -20.0 20.0 °C UT
PUH1
Offset for the winter setpoint from
digital input
-2.0 -20.0 20.0 °C UT
PSd1 Change the password at User level. 0 -999 9999 UT
Level
2
MAINTENANCE MENU
FUNCTION MODES
PM00
Set the maximum number of
operating hours of the compressors.
When this limit is exceeded, the
relative alarm goes off.
2000 0 9999
Hours
x10
MA-F
PM01,
PM02
PM03
PM04
PM05
PM06
View the number of operating hours
of the compressors. A parameter for
each compressor.
0 0 9999
Hours
x10
MA-F
PM30
Set the maximum number of
operating hours of the pumps. When
this limit is exceeded, the relative
alarm goes off.
2000 0 9999
Hours
x10
MA-F
PM31
View the number of operating hours
of the first pump.
0 0 9999
Hours
x10
MA-F
PM32
View the number of operating hours
of the second pump.
0 0 9999
Hours
x10
MA-F
PM33
View the number of operating hours
of the first source pump.
0 0 9999
Hours
x10
MA-F
PM34
View the number of operating hours
of the second source pump.
0 0 9999
Hours
x10
MA-F
PM40
Set the maximum number of
operating hours of the fans. When
this limit is exceeded, the relative
alarm goes off.
2000 0 9999
Hours
x10
MA-F
PM41
View the number of operating hours
of the first fan or inverter in Circuit #
1.
0 0 9999
Hours
x10 MA-F
PM42
View the number of operating hours
of the second fan or inverter in Circuit
# 2.
0 0 9999
Hours
x10 MA-F