Page #24 background imageLoading...
Page #24 background image
EVCO S.p.A.
c-pro 3 nano CHIL | Application manual ver. 1.0 | Code 144CP3NCHE104
page 24 of 90
PM43
View the number of operating hours
of the free-cooling fan
0 0 9999
Hours
x10
MA-F
PM90 Date of last maintenance job - MA-F
MANUAL
PM11,
PM12
PM13
PM14
PM15
PM16
Enable manual/automatic operation of
the compressor.
0: Auto – normal operation
1: Manu – manual operation
One for each compressor.
0 0 1 MA-M
PM21
PM22
PM23
PM24
PM25
PM26
During manual operation, force the
start-up/shutdown of the compressor.
0: turn off compressor (OFF)
1: turn on compressor (ON)
One for each compressor.
0 0 1 MA-M
PM35
Enable manual/automatic operation of
the pump # 1.
0: Auto – normal operation
1: Manu – manual operation
0 0 1 MA-M
PM36
Enable manual/automatic operation of
the pump # 2.
0: Auto – normal operation
1: Manu – manual operation
0 0 1 MA-M
PM37
During manual operation, force the
start-up/shutdown of the pump #1
0 0 1 MA-M
PM38
During manual operation, force the
start-up/shutdown of the pump #2
0 0 1 MA-M
PM45
Enable manual/automatic operation of
the pump # 1.
0: Auto – normal operation
1: Manu – manual operation
0 0 1 MA-M Only for the water/water unit
PM46
Enable manual/automatic operation of
the source pump # 2.
0: Auto – normal operation
1: Manu – manual operation
0 0 1 MA-M Only for the water/water unit
PM47
During manual operation, force the
start-up/shutdown of the source
pump #1
0 0 1 MA-M Only for the water/water unit
PM48
During manual operation, force the
start-up/shutdown of the source
pump #2
0 0 1 MA-M Only for the water/water unit
PM51
Enable the manual/automatic
operation of the condensation fan in
Circuit # 1.
0: Auto – normal operation
1: Manu – manual operation
0 0 1 MA-M
PM52
Enable the manual/automatic
operation of the condensation fan in
Circuit # 2.
0: Auto – normal operation
1: Manu – manual operation
0 0 1 MA-M
PM61 During the manual operation, force 0 0 100 % MA-M With PF01=1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Evco c-pro 3 nano CHIL and is the answer not in the manual?

Evco c-pro 3 nano CHIL Specifications

General IconGeneral
BrandEvco
Modelc-pro 3 nano CHIL
CategoryController
LanguageEnglish

Related product manuals