EVCO S.p.A.
c-pro 3 nano CHIL | Application manual ver. 1.0 | Code 144CP3NCHE104
page 25 of 90
the start-up/shutdown of the
condensation fan in Circuit # 1.
(Modulating control)
PM62
During the manual operation, force
the start-up/shutdown of the
condensation fan in Circuit # 2.
0 0 100 % MA-M
With PF01=1
(Modulating control)
PM63
During the manual operation, force
the start-up/shutdown of the
condensation fan in Circuit # 1.
0 0 1 MA-M
With PF01=0
(Single phase control)
PM64
During the manual operation, force
the start-up/shutdown of the
condensation fan in Circuit # 2.
0 0 1 MA-M
With PF01=0
(Single phase control)
PM65
Enable the manual/automatic
operation of the free-cooling fan:
0: Auto – normal operation
1: Manu – manual operation
0 0 1 MA-M
Only for the air/water chillers
when PG13>0
PM66
During the manual operation, force
the value of the free-cooling fan
0 0 100 % MA-M
Only for the air/water chillers
when PG13=1
PM67
During the manual operation, force
the value of the free-cooling fan
0 0 1 MA-M
Only for the air/water chillers
when PG13=2
CALIBRATION
PM71
External temperature probe
calibration
0.0 -10.0 10.0 °C MA-C
PM72
Free-cooling input temperature probe
calibration
0.0 -10.0 10.0 °C MA-C
PM73 Input temperature probe calibration 0.0 -10.0 10.0 °C MA-C
PM74
Output temperature probe calibration
circuit 1
0.0 -10.0 10.0 °C MA-C
PM75
Output temperature probe calibration
circuit 2
0.0 -10.0 10.0 °C MA-C
PM76
Output source temperature probe
calibration circuit 1
0.0 -10.0 10.0 °C MA-C
PM77
Output source temperature probe
calibration circuit 2
0.0 -10.0 10.0 °C MA-C
PM78
Temperature probe calibration of the
coil circuit 1
0.0 -10.0 10.0 °C MA-C
PM79
Temperature probe calibration of the
coil circuit 2
0.0 -10.0 10.0 °C MA-C
PM80
Calibration of the temperature probe
of the discharge compressors circuit 1
0.0 -10.0 10.0 °C MA-C
PM81
Calibration of the temperature probe
of the discharge compressors circuit 2
0.0 -10.0 10.0 °C MA-C
PM82
Remote auxiliary temperature probe
calibration
0.0 -10.0 10.0 °C MA-C
PM83
Condensation pressure probe
calibration circuit 1
0.0 -20.0 20.0 Bar MA-C
PM84
Condensation pressure probe
calibration circuit 2
0.0 -20.0 20.0 Bar MA-C
PM85
Evaporation pressure probe
calibration circuit 1
0.0 -20.0 20.0 Bar MA-C
PM86 Evaporation pressure probe 0.0 -20.0 20.0 Bar MA-C