EVCO S.p.A.
c-pro 3 nano CHIL | Application manual ver. 1.0 | Code 144CP3NCHE104
page 35 of 90
PG04 Enable the Real Time Clock RTC 1 0 1 CO-W
PG05
Enable the presence of the EVCM
modules (1 per circuit)
Yes (1) No (0) Yes (1) CO-W
PG09 Set the number of pumps. 1 1 2 CO-W
PG10
Set the number of source pumps (for
the water/water unit).
1 1 2 CO-W Only for the water/water unit
PG11
Enable single condensation:
0: No (2 fans)
1: Yes (1 fan)
No (0) No (0) Yes (1) CO-W
For the water/water unit
determines whether there are
1/2 heat source exchangers
PG12
Enable loads single/dual exchanger:
0: No (2)
1: Yes (1)
Yes (1) No (0) Yes (1) CO-W
Determine whether there are
1/2 heat sink exchangers
PG13
Set the air circuit type for free-cooling
0: Single with the condensation
1: Separate with AO fan
2: Separate with DO fan
1 0 2 CO-W
Only for the air/water unit of
the chiller
PG14
Enable the single/dual heat source
exchanger:
0: No (2)
1: Yes (1)
Yes (1) No (0) Yes (1) CO-W
Determine whether there are
1/2 heat source exchangers
PSd4 Manufacturer level password 0 -999 9999 CO
HARDWARE CONFIGURATION
NANO+
HA01
HA02
HA08
HA09
Set the probes linked to the analogue
inputs 1, 2, 3, 7, 8, 9 of the controller
3
4
15
13
0 68
CO-
HW
See Table
Config. AI
HA03
HA04
HA05
HA06
HA07
Set the probes linked to the analogue
inputs 4,5,6 of the manufacturer
0
10
0
37
11
0 56
CO-
HW
HA11
HA12
HA16
HA17
HA18
HA19
Set the probes linked to the analogue
inputs 1, 2, 3, 7, 8, 9 of the
expansion
0 0 68
CO-
HW
HA13
HA14
HA15
Set the probes linked to the analogue
inputs 4,5,6 of the expansion
0
0
0
0 56
CO-
HW
HB01
…
HB05
Set which digital resources to link to
the controller's digital inputs
27
7
31
23
21
0 44
CO-
HW
See Table
Config. DI
HB06
…
HB14
Set which digital resources to link to
the expansion's digital inputs
0 0 44
CO-
HW
HC01
HC02
HC03
They set which analogue resources to
connect to the analogue outputs
1, 2, 3, 4 of the controller
8
9
0
0 9
CO-
HW
See Table
Config. AO