0 = seconds
1 = minutes
Par. Min. Max. Unit Default Compressor protection
C0 0 240 min 0 compressor switch-on delay from instrument switch-on
C1 0 240 min 2 minimum time between two compressor switch-ons (3)
C2 0 240 min 0 compressor switch off minimum duration
C3 0 240 s 0 minimum duration of compressor switch on time
C4 0 240 min 0
compressor forced switch-on duration and start of recovery,
proving and baking delay phases
C6 0 199 °C 70
condenser temperature above which the blocked
overheated condenser alarm is activated (“COH” code)
C7 0 199 °C 80
condenser temperature above which the blocked
compressor alarm is activated (“CSd” code)
C8 0 15 min 1 blocked compressor alarm delay (“CSd”code)
Par. Min. Max. Unit Default Defrosting
d0 0 99 h 6
defrosting interval
0 = defrosting will never be activated at intervals
d1 0 1 - - - - 0
type of defrosting
0 = electrical (the compressor will be switched off during
defrosting, the defrosting output will be activated
and the evaporator fan will be switched off)
1 = hot gas (the compressor will be switched on during
defrosting, the defrosting output will be activated
and the evaporator fan will be switched off)
d2 -99 99 °C 8
defrosting end temperature (evaporator temperature); see
also parameter d3
d3 0 99 min 30
if parameter P3 is set at 0, duration of defrosting
if parameter P3 is set at 1, maximum duration of
defrosting; see also parameter d2
0 = defrosting will never be activated
d5 0 99 min 30
defrosting delay from start-up of storing/manual
refrigeration
0 = defrosting will be started on expiry of the time
established with parameter d0
d7 0 15 min 2
dripping duration (the compressor and the evaporator fan
remain off during dripping and the defrosting output will be
deactivated)
d15 0 99 min 0
minimum duration of compressor switch-on on activation of
defrosting so these can be activated (only if parameter d1
is set at 1)
Par. Min. Max. Unit Default Temperature alarms