F23 0 100 % 35 evaporator fan min speed calibration value
F24 0 100 % 65 evaporator fan max speed calibration value
Par. Min. Max. Unit Default Digital inputs
i0 0 2 - - - - 2
effect caused by opening the door, i.e. by activation of the
door micro switch
0 = no effect
1 = the compressor, the evaporator fan
and the heater
will be switched off and the cabinet will be switched
on
2 = the evaporator fan and the heater will be switched
off and the cabinet light will be switched on
i1 0 1 - - - - 1
type of door micro switch input contact
0 = normally open (input active with closed contact)
1 = normally closed (input active with open contact)
i2 -1 120 min 5
door open alarm signalling delay (“id” code)
-1 = the alarm will not be signalled
i3 0 1 - - - - 1
effect caused by the activation of the high pressure input
0 = no effect
1 = the compressor and the evaporator fan will be
switched off and the condenser fan will be switched
on
i4 0 1 - - - - 0
type of high pressure input 1
0 = normally open (input active with closed contact)
1 = normally closed (input active with open contact)
i5 -1 240 s 5
high pressure alarm signalling delay (“HP code)
-1 = the alarm will not be signalled
i6 0 2 - - - - 2
effect caused by the activation of the low pressure input
0 = no effect
t1 = alarm the compressor and the evaporator fan will be
off
2 = pump-down management and alarm. In the
compressor switch-off phase, the intervention of the
digital input will switch the compressor output off to
end the pump-down phase . During the cooling plant
activation phases, the intervention of the digital
input will switch the compressor and the evaporator
fan off
i7 0 1 - - - - 0
type of low pressure input 1
0 = normally open (input active with closed contact)
1 = normally closed (input active with open contact)
i8 -1 240 s 10
low pressure alarm signalling delay (“LP” code)
-1 = the alarm will not be signalled
i9 0 240 s 40
low pressure switch rearm time on compressor switch on
(only if i6 =2)
i10 0 1 - - - - 1
type of circuit breaker protection input contact
0 = normally open (input active with closed contact)