746 E R 30 732099 - Rev.D
Translation of the original instructions
ENGLISH
OPEN during closing, causes it to reopen.
If the closing photocells are triggered during the pause time, they
reset the pause time.
■ S AUTOMATIC SAFETY
This logic only requires the OPEN command to be used.
OPEN if the automation is closed, causes it to open. The automation
closes automatically after the pause time has elapsed.
OPEN during the pause, causes it to close.
OPEN during opening, causes it to close.
OPEN during closing, causes it to reopen.
If the closing photocells are triggered during the pause time, they
close the automation 5 seconds after they have been released.
■
E SEMI-AUTOMATIC
This logic only requires the OPEN command to be used.
OPEN if the automation is closed, causes it to open.
OPEN if the automation is open, causes it to close.
OPEN during opening, stops it and the followingOPEN command
closes it.
OPEN during closing, causes it to reopen.
■ EP SEMI-AUTOMATIC STEP-BY-STEP
This logic only requires the OPEN command to be used.
OPEN if the automation is closed, causes it to open.
OPEN if the automation is open, causes it to close.
OPEN during opening or closing, stops it and the following OPEN
command reverses the direction.
■ C DEAD-MAN
This logic requires the maintained OPEN and CLOSE commands to
be used.
CLOSE is obtained by the connection to terminal OPEN B (partial open-
ing is not available). The controls must be activated intentionally and
the automation must be visible.
Maintained OPEN opens the automation.
Maintained CLOSE closes the automation.
Movement stops if the photocells are triggered.
■ b SEMI-AUTOMATIC b
This logic requires the OPEN and CLOSE commands to be used.
CLOSE is obtained by the connection to terminal OPEN B (partial
opening is not available).
OPEN if the automation is closed, causes it to open.
CLOSE if the automation is open, causes it to close.
CLOSE during opening, has no effect.
OPEN during closing, causes it to reopen.
Movement stops if the photocells are triggered.
■ bC MIXED (b during opening / C during closing)
This logic requires the OPEN impulse command to open and the
maintained CLOSE command to close.
CLOSE is obtained by the connection to terminal OPEN B (partial
opening is not available). The CLOSE command must be activated
intentionally and the automation must be visible.
OPEN opens the automation.
Maintained CLOSE closes the automation.
Maintained CLOSE during opening has no effect.
OPEN during closing, causes it to reopen.
Movement stops if the photocells are triggered.
ADVANCED FUNCTION Default
Ph
Closing photocells operation (FSW CL)
Y stop, reverse to open when released
no reverse, immediate open
no
oP
Opening photocells operation (FSW OP)
Y reverse, immediate close
no stop with opening when released
no
EC
Encoder obstacle detection sensitivity
00 obstacle detection not enabled
01 (max sensitivity)… 99 (minimum sensitivity)
99
rP
Pre-limit switch deceleration
00 not enabled
01… 99 duration of slowdown in steps of 0.1 s (if the encoder is not
enabled) or in steps of 1 revolution of the motor (the adjustment is more
precise if the encoder is enabled)
10
rA
Post-limit switch deceleration
00 not enabled
01… 20 duration of slowdown in steps of 0.1 s (if the encoder is not
enabled) or in steps of 1 revolution of the motor (the adjustment is more
precise if the encoder is enabled)
02
PO
Partial opening (OPEN B)
level
01… 20
05
t
Time-out
00…4.1 adjustment in steps of 1 s from 0 to 59, then in steps of 10 s
E.g. 41 = 41 s ; 4.1 = 4 min and 10 s (max time)
2.0
AS
Request assistance alert
Y enabled
no not enabled
no
nc
Cycle counter
00…99 (thousands of cycles)
00
St
Exit from programming mode and display the status of the automation:
00 Closed
01 Opening
02 Stopped
03 Open
04 Open in pause
05 Failsafe test failed
06 Closing
07 Reversing
08 Photocells tripped
8.3 OPERATING LOGICS
The STOP command has priority over all other commands and stops the
automation in all the logics. The CLOSE command closes the automation if
it is open and stops the automation if it is opening.
■ A AUTOMATIC
This logic only requires the OPEN command to be used.
OPEN when the automation is closed, causes it to open. The auto-
mation closes automatically after the pause time has elapsed.
OPEN during the pause, resets the pause time.
OPEN during opening, is ignored.
OPEN during closing, causes it to reopen.
If the closing photocells are triggered during the pause time, they
reset the pause time.
■ AP AUTOMATIC STEP-BY-STEP
This logic only requires the OPEN command to be used.
OPEN if the automation is closed, causes it to open. The automation
closes automatically after the pause time has elapsed.
OPEN during the pause, stops it and the following OPEN command
closes it.
OPEN during opening, stops it and the following OPEN command
closes it.