746 E R 35 732099 - Rev.D
Translation of the original instructions
ENGLISH
11. DIAGNOSTICS
11.1 CONNECTION STATUS
Move the gate to its halfway position, turn the power on and check the
LEDs on the board (10): the status of the LEDs must correspond to
those indicated in bold. Otherwise, check the connections.
11.2 STATUS OF THE AUTOMATION
When the board is not being programmed, 2 digits, which indicate
the status of the automation, are shown on the display (11).
11.3 REQUEST ASSISTANCE ALERT
If enabled in advanced programming, the alert is activated when the
scheduled maintenance counter reaches zero.
The alert consists of the flashing light pre-flashing for 2 s before each
movement.
1. Enable the alert in advanced programming: function
AS= Y
2. Set the cycle counter in advanced programming: function nc.
- The counter corresponds to thousands of cycles and decreases
every time 1000 work cycles have been carried out, the remaining
cycles are indicated in thousands.
10 LEDs on the board
bold indicates the condition of the LEDs with the board powered, the gate
at its halfway position and no connected device active.
LED
FC1 Limit switch 1 not engaged engaged
FC2 Limit switch 2 not engaged engaged
OPEN B Partial opening command active not active
OPEN A Total opening command active not active
FSW OP Opening photocells not engaged engaged
FSW CL Closing photocells not engaged engaged
STOP Stop not active active
SAFE Sensitive edges not active active
ENCODER
Flashes when moving
off (contact open) on (contact closed) flashing
11 Status of the automation
Display
00
Closed
05
Failsafe test failed
01
Opening
06
Closing
02
Stopped
07
Reversing
03
Open
08
Photocells triggered
04
Open in pause