31
B614 31 532297 - Rev.D
OUT 4
OUT 3
OUT 2
OUT 1
1
2
3
4
5
6
1
2
5
4
3
1
2
OPEN
+24V
GND
EMER
+24V
GND
STOP
CLOSE
J6
J6 J20
OPEN
1
2
3
4
5
6
+24V
GND
EMER
STOP
CLOSE
5
6
6
TXRX
5.2 CONNECTIONS
F
Before making electrical connections, turn off power
to the barrier. If the disconnect switch is not in
view, apply a warning sign stating “WARNING - Main-
tenance in Progress”.
In Master-Slave configuration see the chapter § 9.
CONTROL DEVICES
(31) Connect the devices to the terminal block J6
of the board.
Multiple NO contacts on same input must be con-
nected in parallel. Multiple NC contacts on same input
must be connected in series.
TERMINAL BLOCK J6:
1
OPEN
NO contact, connect a pushbutton or other pulse
generator that commands the opening of the barrier,
by closing a contact
2
CLOSE
NO contact, connect a pushbutton or other pulse
generator that commands the closing of the barrier,
by closing a contact
3
STOP
Configured as STOP (default):
NC contact, connect a pushbutton or other pulse
generator that commands the stopping of the barrier,
by opening a contact
If NO device is connected, jump the
input to
GND
FSW-CL
Configured as FSW-CL (see SP function in Advanced
programming):
NC contact, connect a photocell or other device that
commands the inversion on opening, by opening a
contact during closing
If NO device is connected, jump the
input to GND
4 EMER
NC contact, connect a pushbutton or other pulse
generator that commands the emergency opening of
the barrier, by opening a contact
If NO device is connected, jump the
input to GND
7 GND
Accessories power supply negative and common
contact (1 A max.)
8-9 + Accessories power supply positive 24 V
"
(1 A max.).
STOP input configured as FSW-CL
The STOP input can be configured as safety (FSW-CL).
Connect the negative of the transmitter (TX) powe
r
supply of the photocells to an OUT output configured
as Fail-Safe. In this way the operating condition of
the photocells is checked before each closing: the
test consists in breaking the power supply to the TX