FAAC B614 - Connections; Control Devices

FAAC B614
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
31
B614 31 532297 - Rev.D
OUT 4
OUT 3
OUT 2
OUT 1
1
2
3
4
5
6
1
2
5
4
3
1
2
OPEN
+24V
GND
EMER
+24V
GND
STOP
CLOSE
J6
J6 J20
OPEN
1
2
3
4
5
6
+24V
GND
EMER
STOP
CLOSE
5
6
6
TXRX
5.2 CONNECTIONS
F
Before making electrical connections, turn off power
to the barrier. If the disconnect switch is not in
view, apply a warning sign stating “WARNING - Main-
tenance in Progress”.
In Master-Slave configuration see the chapter § 9.
CONTROL DEVICES
(31) Connect the devices to the terminal block J6
of the board.
Multiple NO contacts on same input must be con-
nected in parallel. Multiple NC contacts on same input
must be connected in series.
TERMINAL BLOCK J6:
1
OPEN
NO contact, connect a pushbutton or other pulse
generator that commands the opening of the barrier,
by closing a contact
2
CLOSE
NO contact, connect a pushbutton or other pulse
generator that commands the closing of the barrier,
by closing a contact
3
STOP
Configured as STOP (default):
NC contact, connect a pushbutton or other pulse
generator that commands the stopping of the barrier,
by opening a contact
If NO device is connected, jump the
input to
GND
FSW-CL
Configured as FSW-CL (see SP function in Advanced
programming):
NC contact, connect a photocell or other device that
commands the inversion on opening, by opening a
contact during closing
If NO device is connected, jump the
input to GND
4 EMER
NC contact, connect a pushbutton or other pulse
generator that commands the emergency opening of
the barrier, by opening a contact
If NO device is connected, jump the
input to GND
7 GND
Accessories power supply negative and common
contact (1 A max.)
8-9 + Accessories power supply positive 24 V
"
(1 A max.).
STOP input configured as FSW-CL
The STOP input can be configured as safety (FSW-CL).
Connect the negative of the transmitter (TX) powe
r
supply of the photocells to an OUT output configured
as Fail-Safe. In this way the operating condition of
the photocells is checked before each closing: the
test consists in breaking the power supply to the TX