6.3 SETUP
The set-up procedure enables the limits positions to
be memorised.
The system needs to be set-up:
- When the automation system is first started
- When the board has been replaced
- Each time the display shows
50 flashing and the
automation system does not work
- Following any variation in the position of the
positive stops.
How to perform the set-up:
!
During the SET-UP, the safety devices are ignored,
keep away and stop anyone from approaching the
automation system until the end of the procedure
The SET-UP MUST be performed:
- with the mains power switched on
- with the automation system functioning normally
- with the
STOP/EMER inputs not active
1. Select parameter
tL in Basic Programming, the
display shows
--.:
2. Keep the buttons pressed
+
and
-
about 3
seconds. When
S1 appears flashing, release the
buttons. The arm begins to close and stops when
it reaches the stop.
3.
S2
flashes on the display. The arm remains in the
close position for a couple of seconds.
4.
S3 flashes on the display. The arm begins to open
and stops when it reaches the stop.
5. The procedure has come to an end and the display
shows the status of the open automation system
(
01).