6.2 OPERATING LOGICS
In all the logics:
- the
STOP command has the priority and stops the
automation system from working
- the
EMERGENCY command has the priority and opens
the automation system.
EP  SEMIAUTOMATIC STEP BY STEP
The EP logic requires the use of just the OPEN com-
mand:
-
OPEN when the barrier is closed, it commands the
opening.
-
OPEN when the barrier is open it commands the
closing.
-
OPEN during the movement it stops
-
OPEN after the stop, it reverses in movement.
The CLOSE command always commands the closing.
A  AUTOMATIC
Logic A only requires the OPEN command:
-
OPEN when the barrier is closed, it commands the
opening. After the pause time, the barrier closes
again automatically.
-
OPEN when the barrier is open in pause mode, it
reloads the pause time. (Even the intervention of
the photocells reloads the pause time)
-
OPEN during opening is ignored.
-
OPEN during opening causes it to open again.
The CLOSE command always commands the closing.
AP  AUTOMATIC STEPBYSTEP
The AP logic requires the use of just the OPEN com-
mand:
-
OPEN when the barrier is closed, it commands the
opening. After the pause time, the barrier closes
again automatically.
-
OPEN when the barrier is open in pause mode it
locks. (Even the intervention of the photocells
during the pause mode reloads the pause time)
-
OPEN during the opening locks.
-
OPEN during opening causes it to open again.
The CLOSE command always commands the closing.
b  SEMIAUTOMATIC B
Logic b requires the use of the OPEN and CLOSE
commands:
-
OPEN when the barrier is closed, it commands the
opening.
-
CLOSE when the barrier is open it commands the
closing.
-
CLOSE during opening it causes reclosing.
-
OPEN during opening causes it to open again.
bC SEMIAUTOMATIC b ON OPENING/ PERSON
PRESENT
C ON CLOSING
bC logic requires the use of the OPEN command on
opening and CLOSE maintained on closing. The
activation of the
CLOSE command on closing must be
intentional and the barrier must be visible.
-
OPEN when the barrier is closed, it commands the
opening.
- Maintained
CLOSE commands the closing.
C  DEADMAN
Logic C requires the use of maintained OPEN and
CLOSE commands. The control must be activated
intentionally and the barrier must be visible.
- Maintained
OPEN commands the opening.
- Maintained
CLOSE commands the closing.
- If the photocells are triggered, movement is
stopped.
P  PARKING
Logic P requires the use of the OPEN and CLOSE
commands:
-
OPEN when the barrier is closed, it commands the
opening.
-
CLOSE when the barrier is open it commands the
closing.
-
CLOSE during opening it causes reclosing after
opening.
-
OPEN during opening causes it to open again.
- The triggering of the photocells during closing
stops the movement, on disengagement the barrier
continues to close.
PA  PARKING AUTOMATIC
Logic PA requires the OPEN and CLOSE commands
to be used.
-
OPEN when the barrier is closed, it commands the
opening. After the pause time, the barrier closes
again automatically.
-
OPEN when the barrier is open in pause mode, it
reloads the pause time. (Even the intervention of
the photocells reloads the pause time)
-
CLOSE when the barrier is open it commands the
closing.
-
CLOSE during opening it causes reclosing after
opening.
-
OPEN during opening causes it to open again.
- The triggering of the photocells during closing
stops the movement, on disengagement the barrier
continues to close.