Working level
for normal daily operation
Switch to level
“Service parameters”
See section 8.1.
E parameters
Code: EA03
These parameters are only used to query ACTUAL states.
Display tank monitoring time counter and values Range Default
Display of...
E1 ... over- / under time temperature / time 1 0…900 min. - - -
E2 ... over- / under time temperature / time 2 0…900 min. - - -
E3 ... over- / under time temperature / time 3 0…900 min. - - -
Based on the error messages F1 - F3, it can be
read here how long the milk temperature has
already been above the respectively set limit value.
E6 ... the last cleaning temperature reached 0…99,9 °C - - -
Displays the maximum temperature during the
last cleaning cycle.
E15 ... voltage battery 0,0V ... 12,0V - - -
Display the current voltagebattery
(Only if optional pack is installed)power
General cooling parameters code: C212
Extended cooling parameters code: D345
General cleaning parameters code: B454
Extended cleaning parameters code: C567
Service parameter s code: EA03
General tank monitor parameters code: 4711
Extended tank monitor parameters code: F94A
Alarm configuration code: FFFF
Configuration code: A384
I/O test parameters code: 10E5
8.6 Level “Service parameters” (E parameters)
8. Setting of parameters
Page 59