8. Setting of parameters
Page 66
Working level
for normal daily operation
A parameters
Code: A384
This configuration is very important and should be the first step when setting the
parameters for a system.
The supports a large number of different system configurations (with or Gala Kool Pro
without robot operation), milk tanks with more than one compressor, different outlet
valves etc.). In total, the control unit supports more functions than there are output
relays and digital inputs on the printed circuit board.
Normally, however, not all functions are used at the same time. When starting configu-
ration please give careful consideration to how you want to allocate all the various
components to the relays and digital inputs.
Allocation of output relays:
In [A1 to A12] the functions needed are assigned to the output relays.
Allocation of digital inputs:
In [A21 to A28] input functions are assigned to the digital inputs.
Incorrectly set parameters can lead to serious malfunctions and damage
to the milk-cooling tank.
General cooling parameters code: C212
Extended cooling parameters code: D345
General cleaning parameters code: B454
Extended cleaning parameters code: C567
Service parameter s code: EA03
General tank monitor parameters code: 4711
Extended tank monitor parameters code: F94A
Alarm configuration code: FFFF
Configuration code: A384
I/O test parameters code: 10E5
Switch to level
“Configuration”
See section 8.1.
8.10 Level “Configuration” (A parameters)