Working level
for normal daily operation
Fault messages tank monitor during cooling mode Range DefaultFault
h20 Target temperature 1 milking F20 0 .. 30,0 °C ,0st 6
(Starting from this point the monitoring of the
over / under temperature begins [h25] + [h29])
h21 Max. ime to reach target temperaturet [h20] 0 .. 999 min. 0 = deactivated 180
h23 Max. vertemperature for a time ( rom cooling start)o f F23 0 .. 30,0 °C 10,0
h24 Max. ime of overtemp (from cooling startt erature ) 0 .. 999 min. 0 = deactivated 180
h25 Max. overtemperature with direct alarm triggering F25 0 .. °C 25,0 99,9
(from 1 milking) st
h27 Min. ndertemperature for a time ( rom cooling start)u f F27 0 .. 30,0 °C 2,0
h28 Max. ime of undertemp (from cooling start) t erature 0 = deactivated 0 .. 999 min. 120
h29 Min. undertemperature with direct alarm triggering 0 .. 30,0 °C 0,5F29
(from 1 milking) st Start the counter from cooling start
h31 Max. cooling interruption 0 = deactivated F31 0 .. 999 min. 60
h32 Max. time in off mode after cleaning F32 0 .. min. 0 = deactivated 5000 600
h33 Min. cleaning cycle F33 0 .. 250 h 78
0 = deactivated
h35 Detergent monitoring alkaline by float switch F35 0 .. 2 0
0 = deactivated,
1 = high aktiv
2 = low aktiv
h36 Detergent monitoring acid by float switch F36 0 .. 2 0
0 = deactivated
1 = high aktiv
2 = low aktiv
h38 Max. temperature difference monitoring sensor 1,0 .. 5,0 2,0F38
during cooling mode
Switch to level
“General tank monitor parameters”
See section 8.1.
h parameters
Code: 4711
General cooling parameters code: C212
Extended cooling parameters code: D345
General cleaning parameters code: B454
Extended cleaning parameters code: C567
Service parameter s code: EA03
General tank monitor parameters code: 4711
Extended tank monitor parameters code: F94A
Alarm configuration code: FFFF
Configuration code: A384
I/O test parameters code: 10E5
8.7 Level “General tank monitor parameters” (h parameters)
8. Setting of parameters
Page 60