FX15 Controller Technical Bulletin
31
Linear 0-20 mA, 20% suppression (0.4-2 mA)
Resistance 2k ohm
A99
NTC 2k2 ohm
Ni1000 Johnson Controls
Ni1000 Johnson Controls Extended
Ni1000 Landis and Gyr®
Ni1000 DIN
Pt1000
Ratiometric
The measurement unit is also configurable, enabling the controller to
propagate the measured value according to the appropriate scale unit via
the network. Available configurable units are:
Temperature
Percentage
Air Pressure
Liquid Pressure
Flow
Concentration
Ampere
Voltage
A configurable filter constant in seconds is performed by the FX15
controller on its Analog Inputs for the reduction of signal instability.
You can configure an additional Anti-Spike filter to limit the rate of
change of the input values to the value indicated by this attribute.
The FX15 controller provides a configurable jumper for (Terminal 13)
+5 V Analog Voltage Power Supply (AVPS), or a +16 V External VDC
supply, for active analog input sensors (see Jumper Details.)
The EXT VDC can supply up to 80 mA for a maximum of four 0/4-20
mA active sensors. The AVPS can supply up to 10 mA for ratiometric
sensors.
Connecting Active 0-10 V Sensors
The FX15 controller can accept all the active temperature, pressure,
flow, and humidity sensors providing 0-10 VDC signals.
Figure 32 shows the connection between an FX15 controller and an
HT-9001 probe.