FX15 Controller Technical Bulletin
47
User Interface
The FX15 controller can be connected to two remote user interfaces,
with the capability to display/edit all the data point and information of
the running application. The user interface application is fully
configurable at design time. The user interface must be of the same
type. The user interfaces are optional, which means that the controller
can work without any display plugged-in.
The configuration is integrated, local; for example: panel mount (up to
3 m [9.8 ft]). Or the configuration is remote; for example: wall mount
(up to 1km [0.6 mi]).
integrated: directly plugged on top of the controller
local: up to 3 m (9.8 ft) from the controller, power supply, and data
communication via the flat telephone cable included in the
LP-KIT007-000C
remote: up to 300 m (984 ft) from the controller.
The display must be independently powered; the data
communication occurs via a 3-pole shielded cable (not provided)
connected to the Remote Display Connection of the FX15
controller.
The FX15 controller can support one integrated user interface or one
panel mount (or wall mount) user interface. Or it can support one panel
mount display and one wall mount user interface. For the panel mount
connection, use the cable connection kit (LP-KIT007-000C), 3 m
(9.8 ft) long, with a phone jack on the MUI side and a screw connector
on the FX15 controller side.
The user interface models connectable to the FX15 controller are:
LP-DIS65P10-0C: Large User Interface (LUI), panel, flush mount
or hand-held, 4x20 backlit LCD, IP54, extended temperature range
of -20 to +50°C (68 to 122°F), standard front-plate. The front-plate
is fully customizable upon minimum order.