FX16 Master Controller Technical Bulletin
122
Table 40: Analog Outputs (AO)
Terminal
Channel Type Remark/Application
TB7
AO1, AO2 0 -10 VDC
FX16D/FX16X:
1.5 mA
FX16X Rev. A:
5 mA
Used to drive motor actuators,
power triacs, frequency drives.
16 bit resolution.
TB8
AO3, AO4 0 -10 VDC
FX16D/FX16X:
1.5 mA
FX16X Rev. A:
5 mA
Used to drive motor actuators,
power triacs, frequency drives.
16 bit resolution.
79, 80
AO V~ Hot
AO V~ Com
24 VAC FX16 (not Rev. A): for isolation
of AOs from the microprocessor
a separate 24 VAC power
supply is required
FX16 Master Controller
Table 41: FX16 Master Controller
Product FX16D Master Controller
FX16X Master Controller Extended Temperature Range
FX16X Rev A Master Controller Extended Temp. Range
Power Supply
24 VAC ±15%, 50/60 Hz - Class 2 Power Supply
Power Consumption
15 VA at max. load
Internal Fuse
2 A, 250 V
Protection Class
IP 20 IEC60529
Isolation
See Isolation Diagram.
Ambient Operating Conditions FX16D and integral display: -20°C (-4°F) to +50°C (122°F) ,10 to 95%
RH (noncondensing)
FX16X Extended Temperature Range: -40°C (-40°F) to 60°C (140°F),
10 to 95% RH (noncondensing)
Ambient Storage Conditions
-40°C (-40°F) to +70°C (158°F),10 to 95% rH (noncondensing)
Dimensions (H x W x D)
142 mm (5.6 in.) x 215 mm (8.5 in.) x 49 mm (1.9 in.)
With display: 142 mm (5.6 in.) x 215 mm (8.5 in.) x 66 mm (2.6 in.)
Weight (with package)
0.74 kg (1.6 lb)
I/O ratings
See Ordering Codes.
Connection Terminals for
Signals and Power Supply
Screw terminals for max. 1 x 1.5 mm
2
, 16 AWG wires.
N2 Open Bus Connection
terminals
Screw terminals, cable size 0.5 mm to 1.5 mm
2
, 24 AWG to 16 AWG.
Belden® cable, 4-core twisted pair with shield
LON Network Connection
terminals
Screw terminals, cable size 0.5 mm to 1.5 mm
2
, 24 AWG to 16 AWG.
Belden cable, 2-core twisted pair with shield
Connection for Extension Bus
and Remote Display
Screw terminals, cable size 0.5 mm to 1.5 mm
2
, 24 AWG to 16 AWG.
Belden cable, 4-core, twisted pair with shield
Continued on next page …