FX16 Master Controller Technical Bulletin
44
Inputs and Outputs Concepts
Analog Inputs
The FX16 Master Controller accepts six high-resolution, universal
analog inputs. You can configure each of them as Active or Passive by
the application software and jumper configurations.
Digital Inputs
The FX16 Master Controller accepts eight opto-isolated digital (binary)
inputs from potential free contact. With the input filter set at 50 Hz, a
transition counter (minimum 10 ms ON and minimum 10 ms OFF) is
configured in the control application for any one or more of the digital
inputs.
Analog Outputs
The FX16 Master Controller provides four opto-isolated analog outputs,
0-10 V at 1.5 mA (5 mA for Rev. A controllers).
Digital Outputs
The FX16 Master Controller provides nine digital (binary) outputs,
available in two hardware configurations with either:
• 9 relays
• 4 relays and 5 triacs