FX16 Master Controller Technical Bulletin
14
Consider the following information when you work with the
connections details for FX slave controllers:
FX16 supports a maximum of 16 Facility Explorer slave controllers.
All slave controllers may be in a Distributed Application or
monitored by a Gateway Object, or you can use any combination
that does not exceed 16 devices.
Slave model types for a Distributed Application: FX05 Advanced,
FX06, FX07, FX14, FX10 Advanced, FX15 Classic and FX15
Universal
An FX controller used as a slave must have an RS-485 N2 Open
plug-in communication card installed.
Slave model types for a Gateway Object: FX controller with N2
communication card, N2 Open Vendor (VND) device, or System 91
N2 controller (DX-9100 or TC-910x).
The appropriate N2 bus serial address must be set on each slave
device.
Maximum bus length is 1,200 m (4,000 ft).
Install a repeater (for example, RP-9100-810x) to regenerate the
RS-485 signal. You install the repeater in case more than
31 N2 devices are connected on the local link extension bus and/or
the local link extension bus length is more than 1,200 m (4,000 ft).
Install 220 ohm end-of-line resistors at each end of the bus line
when the bus length is greater than 100 m (330 ft). When the bus
length is fewer than 100 m (330 ft), insert only one 220 ohm resistor
at the FX16 Master Controller end only.
The distributed application is downloaded to the FX16 Master
Controller. Then the FX16 Master Controller downloads the specific
parts of the application to the corresponding FX slaves.
Devices connected and monitored by the Gateway object must be
programmed and/or configured independently.
Slave devices can coexist with XT91/XP91 modules on the local
link extension bus.