FX16 Master Controller Technical Bulletin
48
• Resistance 2 k ohm
• A99
• NTC 2.2 k ohm
• NTC 10 k ohm
• Ni1000 JC
• Ni1000 JC Extended
• Ni1000 Siemens® (Landis® and Gyr®)
• Ni1000 DIN
• Pt1000
• Ratiometric (0.5 to 4.5 V)
The measurement unit of the analog value also enables the controller to
transmit the measured value via the network in the appropriate format.
(This is particularly important for LONWORKS networks.) Available
configurable units include:
• temperature
• percentage
• air pressure
• liquid pressure
• flow
• concentration Pulse Per Minute (PPM)
• ampere
• voltage
A configurable filter object is available in the FX16 application
software. You can create the filter object for each analog input to reduce
signal instability and to limit the rate of change of the input value.
The FX16 Master Controller provides a jumper configurable:
• +5 V Analog Voltage Power Supply (AVPS) or
• +16 V External VDC (EXT VDC)
supply on terminal 13 for active analog input sensors.
The EXT VDC (also on terminals 3 and 8) can supply up to 80 mA for a
maximum of four 0/4-20 mA active sensors. The AVPS can supply up
to 20 mA for ratiometric sensors.