FX16 Master Controller Technical Bulletin
48
Resistance 2 k ohm
A99
NTC 2.2 k ohm
NTC 10 k ohm
Ni1000 JC
Ni1000 JC Extended
Ni1000 Siemens® (Landis® and Gyr®)
Ni1000 DIN
Pt1000
Ratiometric (0.5 to 4.5 V)
The measurement unit of the analog value also enables the controller to
transmit the measured value via the network in the appropriate format.
(This is particularly important for LONWORKS networks.) Available
configurable units include:
temperature
percentage
air pressure
liquid pressure
flow
concentration Pulse Per Minute (PPM)
ampere
voltage
A configurable filter object is available in the FX16 application
software. You can create the filter object for each analog input to reduce
signal instability and to limit the rate of change of the input value.
The FX16 Master Controller provides a jumper configurable:
+5 V Analog Voltage Power Supply (AVPS) or
+16 V External VDC (EXT VDC)
supply on terminal 13 for active analog input sensors.
The EXT VDC (also on terminals 3 and 8) can supply up to 80 mA for a
maximum of four 0/4-20 mA active sensors. The AVPS can supply up
to 20 mA for ratiometric sensors.