FX16 Master Controller Technical Bulletin 73
• XP91D04: four digital inputs and four digital outputs (triac)
• XP91D05: eight digital inputs
• XP91D06: four digital outputs 230 VAC (relay) (Europe only)
• XP91D07: four digital outputs 24 VAC (relay) (North America
only)
Local Link Extension Bus Performances
We conducted a performance test with the following system
configuration.
An FX16 Master Controller performing a distributed application
strategy with:
• 8 slave controllers (FX05/10/15)
• 4 XT/XP modules (64 variables)
• 30 variables shared with each slave (240 total)
• 255 network profile variables and parameters in FX16 controller
• 200 objects running in the application
Table 21shows the measured times in seconds for the transfer of a DI in
the source device to a DO in the destination device.
Table 21: Local Extension Bus Performances
Source Destination Min. Max. Average
FX16
FX10 1.7 6.3 3.5
FX16
FX05 2.1 6.1 3.6
FX16
XT/XP 1.0 6.2 3.2
FX15
FX16 0.7 5.2 2.3
XT/XP
FX16 0.6 8.6 3.9