FX16 Master Controller Technical Bulletin 73
XP91D04: four digital inputs and four digital outputs (triac)
XP91D05: eight digital inputs
XP91D06: four digital outputs 230 VAC (relay) (Europe only)
XP91D07: four digital outputs 24 VAC (relay) (North America
only)
Local Link Extension Bus Performances
We conducted a performance test with the following system
configuration.
An FX16 Master Controller performing a distributed application
strategy with:
8 slave controllers (FX05/10/15)
4 XT/XP modules (64 variables)
30 variables shared with each slave (240 total)
255 network profile variables and parameters in FX16 controller
200 objects running in the application
Table 21shows the measured times in seconds for the transfer of a DI in
the source device to a DO in the destination device.
Table 21: Local Extension Bus Performances
Source Destination Min. Max. Average
FX16
FX10 1.7 6.3 3.5
FX16
FX05 2.1 6.1 3.6
FX16
XT/XP 1.0 6.2 3.2
FX15
FX16 0.7 5.2 2.3
XT/XP
FX16 0.6 8.6 3.9