2. Commissioning
2−31
Festo P.BE−CPX−FB11−EN en 0503b
Example: scanner 1747−SDN (SLC 500 series)
Addressing for example terminal 3 with:
2 input bytes for status bits (strobed data)
The status bits are switched on via the DIL switch 3
(see Tab.1/3)
3 input bytes, input address as from I1.1.8
7 output bytes, output address as from O1.1.0
1
2
8DI 8DI 4DO 8DI 2AO
3
8DO
8 O
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
ÓÓ
Module no.: 01 2 3 4 5 6
1 Field bus node CPX−FB11
(with DIL 3.2 to ON for status bits)
2 Pneumatic interface
(set with DIL switch to 1...8 valve coils)
3 CPA pneumatics
Fig.2/10: CPX example terminal 3
(address example for scanner 1747−SDN, see following table)