EasyManua.ls Logo

Festo CPX-FB11 - Page 86

Festo CPX-FB11
208 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2. Commissioning
2−40
Festo P.BE−CPX−FB11−EN en 0503b
The sequence in Tab.2/6 applies for addressing.
Module
no.
Module Addressing
Input address Output address
0 Field bus node CPX−FB11
1 Digital 8−input module CPX−8DE I1.3.0 ... I1.3.7
2 Digital 4−output module CPX−4DA O1.9.0 ... O1.9.7
*)
3 CP interface
CP I, here: 4 bytes I, 16 bytes O
I1.1.0 ... I1.1.7
I1.1.8 ... I1.1.15
I1.2.0 ... I1.2.7
I1.2.8 ... I1.2.15
O1.1.0 ... O1.1.7
O1.1.8 ... O1.1.15
O1.2.0 ... O1.2.7
O1.2.8 ... O1.2.15
O1.3.0 ... O1.3.7
O1.3.8 ... O1.3.15
O1.4.0 ... O1.4.7
O1.4.8 ... O1.4.15
O1.5.0 ... O1.5.7
O1.5.8 ... O1.5.15
O1.6.0 ... O1.6.7
O1.6.8 ... O1.6.15
O1.7.0 ... O1.7.7
O1.7.8 ... O1.7.15
O1.8.0 ... O1.8.7
O1.8.8 ... O1.8.15
4 Digital multi I/O module
CPX−8DE−8DA
I1.3.7 ... 1.3.15 O1.9.8 ... O1.9.15
5 MPA1 pneumatic module (8DO) O1.10.0 ... O1.10.7
6 MPA1 pneumatic module (8DO) O1.10.8 ... O1.10.15
*)
8 bits occupied, 4 bits used
Tab.2/16: Addressing for scanner 1747−SDN with CPX example terminal 2 (seeFig.2/2)
with modular EDS