Instruction Manual
D103409X012
Installation
May 2013
24
9. Check for clearance between the magnet assembly and the DVC6215 feedback slot.
10. If not already installed, install a vent in the port on the upper diaphragm casing's air supply connection on the
actuator yoke leg.
Air‐to‐Close GX Actuators
6. Using a 5 mm hex wrench, attach the feedback unit to the GX actuator mounting pad.
7. Check for clearance between the magnet assembly and the DVC6215 feedback slot.
8. Install tubing between the actuator casing and the appropriate DVC6215 pneumatic output port.
9. If not already installed, install a vent in the port on the lower diaphragm casing.
Note
D
To convert to air-to-open, install an O‐ring between the feedback units pneumatic output and the actuator mounting pad.
Connect pneumatic tubing from the DVC6205 to the DVC6215. Refer to figure 2‐17.
D
To convert to air-to-close, remove the O‐ring between the feedback units pneumatic output and the actuator mounting pad.
Disconnect the pneumatic tubing from the DVC6205 to the DVC6215. Install tubing between the pneumatic output connection of
the DVC6205 to the pneumatic port on top of the actuator casing.