Instruction Manual
D103409X012
Detailed Setup
May 2013
64
DTravel Alert Hi Hi Point—The value of the travel, in percent (%) of ranged travel, which, when exceeded, sets the Travel
Alert Hi Hi alert.
DTravel Alert Lo Lo Point— The value of the travel, in percent (%) of ranged travel, which, when exceeded, sets the
Travel Alert Lo Lo alert.
Travel Limit Hi/Lo Alerts—Travel Alert Hi is set if the ranged travel rises above the alert high point. Once the alert is set,
the ranged travel must fall below the alert high point by the Travel Alert Deadband before the alert is cleared. See
figure 4‐2.
Travel Alert Lo is set if the ranged travel falls below the alert low point. Once the alert is set, the ranged travel must rise
above the alert low point by the Travel Alert Deadband before the alert is cleared.
DTravel Alert Hi Enable—Yes or No. Activates checking of the ranged travel against the Travel Alert High Point. Factory
default is No.
DTravel Alert Lo Enable—Yes or No. Activates checking of the ranged travel against the Travel Alert Lo Point. Factory
default is No.
DTravel Alert Hi Point— The value of the travel, in percent (%) of ranged travel, which, when exceeded, sets the Travel
Alert Hi alert.
DTravel Alert Lo Point—The value of the travel, in percent (%) of ranged travel, which, when exceeded, sets the Travel
Alert Lo alert.
Travel Limit / Cutoff Alerts
DTravel Limit/Cutoff Hi Alert Enable—Yes or No. Activates the Travel Limit / Cutoff Hi alert.
DTravel Limit/Cutoff Lo Alert Enable—Yes or No. Activates the Travel Limit/Cutoff Lo alert.
DCutoff Hi
Travel Cutoff Hi defines the high cutoff point for the travel in percent(%) of pre‐characterized set point. Above this
cutoff, the travel target is set to 123.0% of the ranged travel. Travel Cutoff Hi is deactivated by setting it to 125.0%.
Pressure Cutoff Hi defines the high cutoff point for the pressure in percent (%) of pre‐characterized set point. Above
this cutoff,the pressure target is set to 123.0%. A Pressure Cutoff Hi of 99.5% is recommended to ensure valve goes
fully open. Pressure Cutoff Hi is deactivated by setting it to 125%
DCutoff Lo
Travel Cutoff Lo defines the low cutoff point for the travel in percent (%)of pre‐characterized set point. Below this
cutoff, the travel target is set to -23%. A Travel Cutoff Lo of 0.5% is recommended to help ensure maximum shutoff
seat loading. Travel Cutoff Lo is deactivated by setting it to-25.0%
Pressure Cutoff Lo defines the low cutoff point for the pressure in percent (%) of pre‐characterized set point. Below
this cutoff,the pressure target is set to -23%. A Pressure Cutoff Lo of 0.5% is recommended to help ensure maximum
shutoff seat loading. Pressure Cutoff Lo is deactivated by setting it to -25.0%
DChange Cutoffs—Allows you to set Cutoff Hi and Cutoff Lo. When a cutoff is set the corresponding travel or pressure
limit is disabled.
DTravel Limit High—Defines the high limit for the travel in percent (%) of ranged travel. It is the maximum allowable
travel (in percent of ranged travel) for the valve. During operation, the travel target will not exceed this limit. When
a Travel Limit High is set, the Travel Cutoff High is deactivated, since only one of these parameters can be active.
Travel Limit High is deactivated by setting it to 125.0%.

Table of Contents

Other manuals for Fisher FIELDVUE DVC6200

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fisher FIELDVUE DVC6200 and is the answer not in the manual?

Fisher FIELDVUE DVC6200 Specifications

General IconGeneral
BrandFisher
ModelFIELDVUE DVC6200
CategoryController
LanguageEnglish

Related product manuals