No. Menu name Specification Description
17_5_2 Function gen.input 2 Writable Alternative0 = None1 =
P2 manual2 = Power failure3 =
External alarm4 = Blocking5 =
Personnel6 = Rain meter7 =
Overflow8 = Low level float9 =
High level float10 = High temp.
P211 = P2 Spare alarmCentral
System TextFunction general input
2
Select function for general input 2.Default is 'High temp. P2'
17_5_3 Function gen.input 3 Writable Alternative0 = None1 =
P3 manual2 = Power failure3 =
External alarm4 = Blocking5 =
Personnel6 = Rain meter7 =
Overflow8 = Low level float9 =
High level float10 = High temp.
P311 = P3 Spare alarmCentral
System TextFunction general input
3
Select function for general input 3.Default is 'High temp. P3'
17_5_4 Function gen.input 4 Writable Alternative0 = None1 =
P4 manual2 = Power failure3 =
External alarm4 = Blocking5 =
Personnel6 = Rain meter7 =
Overflow8 = Low level float9 =
High level float10 = High temp.
P411 = P4 Spare alarmCentral
System TextFunction general input
4
Select function for general input 4.Default is 'High temp. P4'
17_5_5 Function gen.input 5 Writable Alternative0 = None1 =
P1 auto2 = Power failure3 =
External alarm4 = Blocking5 =
Personnel6 = Rain meter7 =
Overflow8 = Low level float9 =
High level float10 = High temp.
P111 = P1 Spare alarmCentral
System TextFunction general input
5
Select function for general input 5.Default is 'Overflow'
17_5_6 Function gen.input 6 Writable Alternative0 = None1 =
P2 auto2 = Power failure3 =
External alarm4 = Blocking5 =
Personnel6 = Rain meter7 =
Overflow8 = Low level float9 =
High level float10 = High temp.
P211 = P2 Spare alarmCentral
System TextFunction general input
6
Select function for general input 6.Default is 'Power failure'
17_5_7 Function gen.input 7 Writable Alternative0 = None1 =
P3 auto2 = Power failure3 =
External alarm4 = Blocking5 =
Personnel6 = Rain meter7 =
Overflow8 = Low level float9 =
High level float10 = High temp.
P311 = P3 Spare alarmCentral
System TextFunction general input
7
Select function for general input 7.Default is 'Low level float'
Appendix A: RTU Descriptions
58 APP 541 User manual