TCA200 Rev171031
22
CALIBRATION
The following program functions are available to view and change once the
calibration password code has been entered:
C1 - Discharge Pressure Sensor Zero Calibration
C2 - Intake Pressure Sensor Zero Calibration
Refer to Calibration Programs.
Calibration Programs
The calibration password code is set from the factory as 1111.
Enter Calibration Password Code
Note: To exit the programming mode press the SILENCE button when the
program code is ashing in the RPM display.
1. Press the SILENCE button and hold it until the RPM display shows four
dashes – – – – and the message display shows enter---- . Release the
button.
2. Press the MENU button within three seconds. The RPM display shows the
number 1000. Each time the MENU button is pressed the rst digit scrolls
up by 1. Set the rst digit to the number desired.
3. Press the SILENCE button to move the curser to the next digit. Press the
MENU button to change the digit.
4. Repeat step 3 and enter the password code 1111.
Result: When a correct code is entered C 1 ashes in the RPM display.
The program revision D.Sensor Set P=0? scrolls in the message display.